Technical Evaluation of the Adequacy of Station Electric Distribution System Voltages for the R.E. Ginna Nuclear Power Station, Unit 1

Technical Evaluation of the Adequacy of Station Electric Distribution System Voltages for the R.E. Ginna Nuclear Power Station, Unit 1

Author:

Publisher:

Published: 1981

Total Pages:

ISBN-13:

DOWNLOAD EBOOK

This report documents the technical evaluation of the adequacy of the station electric distribution system voltages for the R.E. Ginna Nuclear Power Station, Unit 1. The evaluation is to determine if the onsite distribution system, in conjunction with the offsite power sources, has sufficient capacity to automatically start and operate all Class 1E loads within the equipment voltage ratings under certain conditions established by the Nuclear Regulatory Commission. The analysis submitted demonstrates that acceptable voltages will be supplied to the Class 1E equipment under worst case conditions.


Technical-evaluation Report on the Adequacy of Station Electric-distribution-system Voltages for the Prairie Island Nuclear Generating Plant, Units 1 and 2. (Docket Nos. 50-282, 50-306).

Technical-evaluation Report on the Adequacy of Station Electric-distribution-system Voltages for the Prairie Island Nuclear Generating Plant, Units 1 and 2. (Docket Nos. 50-282, 50-306).

Author:

Publisher:

Published: 1982

Total Pages:

ISBN-13:

DOWNLOAD EBOOK

This report documents the technical evaluation of the adequacy of the station electric distribution system voltages for the Prairie Island Nuclear Generating Plant, Units 1 and 2. The evaluation is to determine if the onsite distribution system in conjunction with the offsite power sources has sufficient capacity to automatically start and operate all Class 1E loads within the equipment voltage ratings under certain conditions established by the Nuclear Regulatory Commission. The evaluation finds that with some minor transformer loading modifications, hardware changes and the results of equipment testing and manufacturer data, the offsite sources were demonstrated to supply adequate voltage to the Class 1E equipment under worst case conditions.


Technical Evaluation of the Proposed Design Modifications and Technical Specification Changes for the R.E. Ginna Nuclear Power Plant

Technical Evaluation of the Proposed Design Modifications and Technical Specification Changes for the R.E. Ginna Nuclear Power Plant

Author:

Publisher:

Published: 1980

Total Pages:

ISBN-13:

DOWNLOAD EBOOK

The present design uses undervoltage relays to sense the loss of offsite power. There are no Class 1E loads on the 4160-volt buses. This design consists of two relays per 480-volt Class 1E bus (two Class 1E buses per redundant load group) for the first level of undervoltage protection. An undervoltage condition (loss-of-voltage) will result in isolating the Class 1E buses from all offsite sources, initiating emergency diesel generator start and load shedding on the Class 1E buses, permitting closure of the diesel generator supply breakers, and lastly, the loads will be automatically time-sequenced onto the buses. Actuation begins with loss of voltage to 368 volts (77% of 480 volts). The existing system does not bypass the load-shedding feature once the emergency diesel generators are energizing the Class 1E buses. The licensee has proposed a design change which includes automatic degraded voltage protection. This modification consists of the addition of two time-delayed, undervoltage relays on each 480-volt Class 1E bus, to provide the second level of undervoltage protection.